Characterizing the diffuse vacuum arc voltage for MVDC circuit breaker applications: experiment, data, and empirical model
Plasma Physics and Technology, vol. 12, pp. 197–201
Abstract
Proposed hybrid DC circuit breaker concepts rely on the arc voltage in vacuum interrupters to commutate fault currents to parallel branches. This paper presents an extensive experimental investigation of the diffuse vacuum arc voltage of an industrially manufactured vacuum interrupter which is connected to a Thomson coil actuator. By independently varying the opening speed and arc current, an empirical model describing the diffuse vacuum arc voltage as a function of contact distance and current is derived. The model limits are evaluated by discussing the transition phase towards high-current anode mode formation.
Authors 2
-
Philipp Wienkamp Aachen
Affiliation as printed
IAEW at RWTH Aachen University, Schinkelstrasse 2, 52062 Aachen, Germany
-
Willem Leterme Aachen
Affiliation as printed
IAEW at RWTH Aachen University, Schinkelstrasse 2, 52062 Aachen, Germany
Cited by 1 stored of 1
1 result
No patents citing this paper on Lens.org (checked 2026-10-06).